ZGG40-1000 (3) z Modular Power Supply Surge Protective Devic

Mã sản phẩm : 1490068950


Tư vấn hỗ trợ+84-979933470

Features 1 High discharge capacity and low residual voltage; 
2 Overtemperature protection;  
3 Failure indication and remote signalling alarm dry contact;   
4 IP20, UL94 V0 1 Technical Data

Operating Environment

 

Technical Parameters

 

Circuit Diagram

Configuration

 

Dimensions: 90×54×67 (excluding the remote signalling terminal)

 

 

Standards Complied

IEC 61643-1:2005      Surge protective devices connected to low-voltage distribution systems - Part 1: Technical requirements and testing methods
EN 61643-11/A11:2007  Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power distribution systems
UL 1449 ed3               UL 1449 Third Edition
EN 60950-1:2006       Information technology equipment - Safety - Part 1: General requirements 
YD/T 1235.2-2002      Testing methods for surge protective devices connected to low-voltage distribution systems of telecommunication stations / sites
Operating Environment

Installation, Usage And Maintenance

Installation
1 This product can only be installed and maintained by qualified professionals. The installation position cannot be touched by hands. Ensure that it is uncharged and check whether the SPD is all right before installation. If there’s damage or the display window is red, the SPD can not be used any more; if the window is green, the SPD is normal.
2 The SPD should be installed behind the fuse (FU1) of the power supply circuit, with the capacity of the fuse not exceeding 125A gL/gG; otherwise another fuse (FU2) lower than 125A gL/gG should be provided in the surge protection branch circuit. 
3 Refer to Fig. 3 for connection according to the marks on the SPD. The sectional-area of connecting line must be larger than 16mm2, as short as possible. 
4 Connection of remote signalling alarm: the SPD is provided with remote signalling alarm interfaces (1 and 2 normally closed; 2 and 3 abnormally open), applicable for remote centralized monitoring or alarm.

Wiring Diagram


Usage and Maintenance
1 After failure, the SPD shall be automatically disconnected with the power supply circuit through the internal thermal fuse system, the display window is changed from “Green” to “Red”, and remote signalling interfaces 1 and 2 are closed and 2 and 3 open. When the degradation indicating window is “Red” or there’s a remote alarm signal, the SPD should be changed immediately.    
2 The display window of the SPD must be checked after the lightning storm