Bộ cấp nguồn SPD mô-đun ZGG40-275

Mã sản phẩm : 1490069365


The ZGG40-275 Modular Power Supply SPD can be used for protection of L-N and L/N-PE. It is applied in the low voltage AC power distribution system, and connected between AC power supply and system equipment in parallel. It can prevent equipment from the impulse surge and transient overvoltage caused by the outside environment (such as lightning, EMI, etc.) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance load, etc.)
 

Hỗ trợ Tư vấn+84-979933470

Tính năng

1 Anti-reverse slot design; 

2 High discharge capacity and low residual voltage; 

3 Overtemperature protection; 

4 Failure indication and centralized remote signalling alarm dry contacts. 

5 IP20, UL94 V0

 

Môi trường hoạt động

 

Thông số kỹ thuật

 

Sơ đồ mạch 

Cấu hình

Overall dimensions: 90mm×18mm×67mm (excluding remote signalling terminals)

 

Các tiêu chuẩn áp dụng

IEC 61643-1:2005      Surge protective devices connected to low-voltage distribution systems - Part 1: Technical requirements and testing methods
EN 61643-11/A11:2007  Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power distribution systems
UL 1449 ed3             UL 1449 Third Edition
EN 60950-1:2006       Information technology equipment - Safety - Part 1: General requirements 
YD/T 1235.2-2002     Testing methods for surge protective devices connected to low-voltage distribution systems of telecommunication stations / sites 

 

Lắp đặt, sử dụng và bảo trì

Lắp đặt

1 This product can only be installed and maintained by qualified professionals. The installation position cannot be touched by hands. Ensure that it is uncharged and check whether the SPD is all right before installation. If there’s damage or the display window is red, the SPD can not be used any more; if the window is green, the SPD is normal. 
2 The SPD should be installed behind the fuse (FU1) of the power supply circuit, with the capacity of the fuse not exceeding 125A gL/gG; otherwise an 80A gL/gG fuse (FU2) should be provided in the surge protection branch circuit. 
3 Refer to Fig. 3 for connection, according to the marks on the SPD. The sectional area of the conductor must be more than 4mm2, as short as possible. 
4 Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (1 and 2 normally closed, and 2 and 3 normally open), applicable for remote centralized monitoring or alarm. 
5 After the connection, check if the module is fitted in. If so, 1 and 2 are closed, and 2 and 3 are open; if not, repress the module.

 

Sơ đồ đi dây:

 

Cách sử dụng và bảo trì:


1 After failure, the SPD shall be automatically disconnected with the power supply circuit through the internal thermal fuse system, the display window changes to “Red” from “Green”, and remote signalling interfaces 1 and 2 are open and 2 and 3 are closed. When the degradation display window is “Red” or there’s a remote alarm signal, the SPD should be changed immediately. 
 

2 The display window of the SPD must be checked after the lightning storm.


TAGS:


Sản phẩm cùng loại