Bộ cấp nguồn SPD mô-đun ZGG40-320 (3+1)

Mã sản phẩm : 1489390240


The ZGG40-320 (3+1) Modular Power Supply SPD is made up of three varistor power supply modules and an air discharge tube power supply module for secondary protection of L-N and N-PE respectively. It is applied in the low voltage AC power distribution system, and connected between AC power supply and system equipment in parallel. It can prevent equipment from the impulse surge and transient overvoltage caused by the outside environment (such as lightning, EMI, etc.) or by the system (such as switching effects of the system, startup or shutoff of the inductance and capacitance load, etc.)
 

Hỗ trợ Tư vấn+84-979933470

Tính năng

1 Anti-reverse slot design; 
2 High discharge capacity and low residual voltage; 
3 Overtemperature protection;  
4 Failure indications and centralized remote signalling alarm dry contact; 
5 IP20, UL94 V0 Technical Data

 

Môi trường hoạt động

 

Các thông số kỹ thuật

 

Sơ đồ mạch

 

Cấu hình

Overall dimensions: 90mm×72mm×67mm (excluding remote signalling terminals)


 

Các tiêu chuẩn áp dụng

IEC 61643-1:2005      Surge protective devices connected to low-voltage distribution systems - Part 1: Technical requirements and testing methods

EN 61643-11/A11:2007  Low-voltage surge protective devices - Part 11: Surge protective devices connected to low-voltage power distribution systems

UL 1449 ed3               UL 1449 Third Edition

EN 60950-1:2006       Information technology equipment - Safety - Part 1: General requirements 

YD/T 1235.2-2002      Testing methods for surge protective devices connected to low-voltage distribution systems of telecommunication stations / sites

 

Lắp đặt, sử dụng và bảo trì

Lắp đặt

1 This product can only be installed and maintained by qualified professionals. The installation position cannot be touched by hands. Ensure that it is uncharged and check whether the SPD is all right before installation. If there’s damage or the display window is red, the SPD can’t be used anymore; if the window is green, the SPD is normal. 
2 The SPD should be installed behind the fuse (FU1) of the power supply circuit, with the capacity of the fuse not exceeding 125A gL/gG; otherwise an 80A gL/gG fuse (FU2) should be provided in the surge protection branch circuit. 
3 Refer to Fig. 3 for connection according to the marks on the SPD (L1 to SPD “L1”, L2 to SPD “L2”, and L3 to SPD “L3”; N to SPD “N”, and “” to PE). The sectional area of the connecting line must be more than 4 mm2 and be as short as possible. 
4 Connection of remote signalling alarm: the SPD is provided with remote signalling interfaces (1 and 2 normally closed, and 2 and 3 normally open), applicable for remote centralized monitoring or alarm. 
5 After the connection, check if the module is fitted in. If so, 1 and 2 are closed, and 2 and 3 are open; if not, repress the module.

 

Sơ đồ đi dây



 

Sử dụng và bảo trì


1 After failure, the SPD shall be automatically disconnected with the power supply circuit through the internal thermal fuse system, the display window changes to “Red” from “Green”, and remote signalling interfaces 1 and 2 are open and 2 and 3 are closed. When the degradation display window is “Red” or there’s a remote alarm signal, the SPD should be changed immediately. 
2 The display window of the SPD must be checked after the lightning storm.

 


TAGS:


Sản phẩm cùng loại